ASTM E2032 Standard Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E 119

Zoom  Zoom Issue Date:2012-02-08   Browse:920
ASTM E2032耐火试验数据的扩展标准指南
ASTM E2032 Standard Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E 119
ASTM E2032耐火试验数据的扩展标准指南

The methods and procedures set forth in this guide relate to the extension of the fire resistance ratings obtained from particular fire tested specimens to constructions that have not been tested.
Users of this guide must have knowledge and understanding of the provisions of Test Method E 119 including those pertaining to conditions of acceptance.
In order to apply some of the principles described in this guide, reference to the original fire test report will be necessary.
In Test Method E 119, the specimens are subjected to specific laboratory fire test exposure conditions. Substitution of different test conditions or changes in the end use conditions have the ability to change the measured fire-test-response characteristics. Therefore, the extensions of data are valid only for the fire test exposure conditions described in Test Method E 119,.
1. Scope
1.1 This guide covers the extension of fire resistance ratings obtained from fire tests performed in accordance with Test Method E 119 to constructions that have not been tested. Test Method E 119 evaluates the duration for which test specimens will contain a fire, retain their standard integrity, or both during a predetermined test exposure.
1.2 This guide is based on principles involving the extension of test data using simple considerations. The acceptance of these principles and their application is based substantially on an analogous worst case proposition.
1.3 These principles are only applicable to temperature conditions represented by the standard time-temperature curve described in Test Method E 119. Test Method E 119 is a fire-test-response standard.
1.4 The types of building constructions which are the subject of this guide are categorized as follows: beams; floor and roof assemblies; columns; and walls and partitions. Floor and roof assemblies include such assemblies with ceiling protective membranes.
1.5 The extension of test data using numerical calculations based on empirical data or theoretical models is not covered in this guide.
1.6 This guide does not cover the substitution of one proprietary material for another proprietary material, or materials for which fire test data are not presently available.
1.7 This guide does not purport to be comprehensive in its treatment of non-proprietary modifications of tested constructions. Engineering evaluation or tests are recommended for assessing modifications not specifically covered in this guide.
1.8 The values stated in SI units are to be regarded as standard.
1.9 This standard is used to determine certain fire-test responses of materials, products, or assemblies to heat and flame under controlled conditions by using results obtained from fire-test-response standards. The results obtained from using this standard do not by themselves constitute measures of fire hazard or fire risk.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
C168 Terminology Relating to Thermal Insulation
C553 Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications
C612 Specification for Mineral Fiber Block and Board Thermal Insulation
E119 Test Methods for Fire Tests of Building Construction and Materials
E176 Terminology of Fire Standards
E631 Terminology of Building Constructions
E1264 Classification for Acoustical Ceiling Products
E1513 Practice for Application of Sprayed Fire-Resistive Materials (SFRMs)
Index Terms
building materials; concrete; fire; fire endurance; fire resistance rating; fire resistance; steel; wood; Beams/girders; Building materials/applications; Column tests; Fire endurance rating; Fire-resistant materials/testing; Fire testing--building materials; Flooring/floor covering systems; Mineral fiber insulation; Roofing materials/applications; Steel; Walls;
 
 