EN 13501-1: Fire Test to Building Material - Classification

Zoom  Zoom Issue Date:2011-07-15   Source:Firetc   Browse:88202
EN13501-1:2007: Fire classification of construction products and building elements-Part1: Classification using data from reaction to fire tests

Fire test center will provide European Standard EN 13501-1 Fire Test to Building Material

EN13501-1:2007: Fire classification of construction products and building elements-Part1: Classification using data from reaction to fire tests

EN 13501-1: Fire Test to Building Material
Scope
With the lucubrate and development in fire science and fire protection, right from the combustion characteristics of flame spread, extend to include the rate of heat release, heat release, toxicity of smoke density and combustion result and other parameters. The classes is EN 13501-1 actively consider the above parameters, therefore more scientific. EN 13501-1 also provides a number of test methods not only consider the actual fire scene, but also consider the end use of the material, which is more practical representation.

EN 13501-1: Fire Test to Building Material
Product
> Construction products, excluding floorings and linear pipe thermal insulation products
> Floorings
> Linear pipe thermal insulation products

EN 13501-1: Fire Test to Building Material-Classification
Construction excluding Flooring
Classification:
A1,A2, B,C,D,E,F
Class F: Test according EN ISO 11925-2 and fail to meet the Class E
Class E: Pass the test according the EN ISO 11925-2
Class D,C,B: Pass the test according EN ISO 11925-2and EN 13823
Class A2: Pass the test according EN 13823 and EN ISO 1182 or EN ISO 1716
Class A1: Pass the test according EN ISO 1182 and EN ISO 1716
Floorings
Classification
A1fl ,A2fl ,Bfl,Cfl,
Dfl,Efl,Ffl
Class Ffl: According EN ISO 11925-2 to test and fail to meet Class Efl
Class Efl: Pass the test specified according to EN ISO 11925-2
Class Dfl,Cfl,Bfl: Pass the test according to EN ISO 11925-2 and ISO 9239-1
Class A2fl: Pass the test according ISO 9239-1 and EN ISO 1182 or EN ISO 1716
Class A1fl: Pass the test according EN ISO 1182 and EN ISO 1716
Linear pipe
Classification
A1L, A2L,BL,CL,DL,EL,FL
Class FL: Test according EN ISO 11925-2 and fail to meet the Class E
Class EL: Pass the test according the EN ISO 11925-2
Class DL,CL,BL: Pass the test according EN ISO 11925-2and EN 13823
Class A2L: Pass the test according EN 13823 and EN ISO 1182 or EN ISO 1716
Class A1L: Pass the test according EN ISO 1182 and EN ISO 1716

EN 13501-1: Fire Test to Building Material-Products
> Insulated materialmineral wool boardglass woolplastic parts, etc
> Textilecurtain, portiere, etc
> FlooringsBamboo flooring, wood flooring, plastic flooring, carpet, rubber flooring, etc
> PipelineAir condition hose, etc

EN 13501-1: Fire Test to Building Material– Reference Standard
> EN 13823, Reaction to fire tests for building products. Building products excluding floorings exposed to the thermal attack by a single burning item
> EN ISO 1182, Reaction to fire tests for building products. Non-combustibility test (ISO 1182:2002)
> EN ISO 1716, Reaction to fire tests for building products. Determination of the heat of combustion (ISO 1716:2002)
> EN ISO 9239-1, Reaction to fire tests for floorings. Part 1: Determination of the burning behaviour using a radiant heat source (ISO 9239-1:2002)
> EN ISO 11925-2, Reaction to fire tests. Ignitability of building products subjected to direct impingement of flame . Part 2: Single-flame source test (ISO 11925-2:2002)

EN 13501-1: Fire Test to Building Material – Similar Standard
> EN ISO 11925-2: Reaction to fire tests – Ignitability of building products subjected to direct impingement of flame – Part 2: Single-flame source test
> EN 13501-1: Fire classification of construction products and building elements- Part1: Classification using data from reaction to fire tests
> NF P 92 - 501: Safety against fire - Building materials - Reaction to fire tests - Radiation test used for rigid materials. or for materials on rigid substrates (flooring and finishes) of all thicknesses. and for flexible materials thicker that 5 mm
> NF P 92 - 503: Safety against fire - Building materials – Reaction to fire tests. Electrical burner test used for flexible materials
> BS 476: Fire tests on building materials and structures
> GB 8624: Classification for burning behavior of building materials and products
> GB 20286: Requirements and mark on burning behavior of fire retarding products and subassemblies in public place

For more detailed information about European Standard EN 13501-1 Fire Test to Building Material.
 
 
[ Fire test center Search ]  [ ]  [ Forword to friends ]  [ Print ]  [ Close ]  [ Back to Top ]

 

 
 
Home | About us | Contact | Terms & Conditions | Copyright | Site Map | Friend link | Guestbook | Old Version | 闽ICP备09009213号
©2013-2015 FIRETC.NET All Rights Reserved   ICP:闽ICP备09009213号-4