PVC Insulated Power cable
1.Main application
This cable is suitable to be installed in transmission and distribution lines of rated voltage up to and including 0.6/1kV.The mechanical and electrical properties of these cables are accordant with GB/T12706-2002 Power cables extruded insulation and their accessories of rated voltages 1kV(Um=1.2kV)up to 35kV(Um=40.5kV)and IEC60502-1997 Extruded insulation power cables and appendices for rated voltages 1kV up to 30kV.
2. Properties of products
2.1 Max. continuous operating temperature of conductor is 70°C.
2.2 Max. Short circuit conductor temperature (max. 5 sec) 160°C.
2.3 The installation temperature should not over 0°C,if the ambient temperature is lower than 0°C,the cable should be preheated ,the bending radius of cable should not less than 10-15 times .
3. Type,de
Type |
De |
Application |
|
Cu |
Al |
||
VV |
VLV |
PVC insulated PVC sheathed power cable |
Suitable for indoor, channels, conduits. Unable to bear mechanical stress. |
VY |
VLY |
PVC insulated PE sheathed power cable |
|
VV22 |
VLV22 |
PVC insulated steel-tape armored PVC sheathed power cable |
Suitable for under ground, can bear mechanical stress, but can not endure large pulling force. |
VV23 |
VLV23 |
PVC insulated steel-tape armored PE sheathed power cable |
|
VV32 |
VLV32 |
PVC insulated fine steel-wire armored PVC sheathed power cable |
Can be installed in vertical well, and bear large mechanical pulling force. |
VV42 |
VLV42 |
PVC insulated steel-wire armored PVC sheathed power cable |
|
VV33 |
VLV33 |
PVC insulated fine steel-wire armored PE sheathed power cable |
|
VV43 |
VLV43 |
PVC insulated steel-wire armored PE sheathed power cable |
Note: We can produce flame-retardant, fire-resistant, anti-termite, LSZH, small smoke and low halogen cables according to customer's requirements. 1. Flame-retardant power cable: add "ZRA-, ZRB-, and ZRC-"before above model no. 2. Fire-resistant power cable: add "NH-"before above model no. 3. LSZH power cable: add "DWZR-"before above model no. 4. Small smoke and low halogen power cable: add "DDZR-"before above model no.