The professional ODH1000 is a 4/8/16 zone, Class B conventional fire alarm control panel, meet the latest UL864&EN54 standard.
Key words: Fire alarm Control Panel,conventional fire alarm control panel, fire alarm panel, fire alarm, FACP, fire alarm system, fire-fighting, fire panel, fire alarm controller, fire alarm control unit
Features
1) 4/8/16 Style B (Class B) Initiating Device Circuits (IDCs).
- All zones accept two-wire smoke detectors and any normally-open contact devices.
- Zones 1 4/8/16 configured as general alarm zones.
2) All circuits are power-limited and supervised, meeting the latest ULC requirements using
fuseless technology.
3) Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
4) NACs may be programmed:
- Silenceable
- Non-Silenceable
- Auto-Silence (program 5 to 20 minutes)
5) 1.25 amps of NAC power
6) 3.0 amps of total system power
7) Alarm, Trouble and Supervisory, Form-C relays standard.
8) 24-volt operation
9) Resettable four-wire smoke detector power @ 500 mA
10) Non-resettable power @ 500 mA
11) Integral battery charger capable of charging up to 18 AH batteries (batteries over 4 AH require
use of the external battery backbox, or ULC listed equivalent).
12) One-man walk-test programmable for silent or audible test
13) Disable/Enable control per IDC
14) Reverse polarity protection
15) Control buttons:
- Mode
- Test
- ACK (Acknowledge) Alarm Silence
- Reset
16) Meet UL864, EN-54 standard.
17) LED indicators:
- AC Power (green & yellow LED)
- Fire Alarm (red LED)
- Trouble (yellow LED)
- Supervisory (yellow LED)
- Signal Silence (yellow LED)
- Battery Power (green & yellow LED)
- Zone Disable (yellow LED)
- NAC Fault (yellow LED)
- NAC Disable (yellow LED)
- 4/8/16 Zone Alarm (one for each zone) (red LED)
- 4/8/16 Zone Trouble (one for each zone) (yellow LED)
- Earth Fault (on circuit board)
- Battery Fault (on circuit board)
- Charger Fault (on circuit board)
Specifications
AC Power: AC220V±10% 50Hz, 2.0 amps, minimum 14 AWG wire (2.0 mm²) with 600-volt
insulation.
Battery: Sealed lead-acid batteries only, Maximum charging circuit: 27.6VDC @ 0.8 amp for
normal flat charge, Maximum battery charger capacity: 18AH battery
NOTE: Two 4AH batteries can be housed in the cabinet.uire
separate & nbp battery box.
Total 24 V system power: 3.0 amps
Notification appliance (signal) power: 2.5 amps
Maximum current per NAC: 1.25 amps (expandable to 2.5 amps)
Auxiliary Outputs: - Resettable four-wire smoke detector power @ 500 mA
- Non-resettable power @ 500 mA
- Integral Form-C Alarm, Trouble and Supervisory relays, rated at: 2.0 amps
@ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive).
NOTE: Total current for auxiliary power outputs and two NACs must not exceed 3.0 amps.
Dimensions: 320×260×80mm (length × width × depth)
Using Environment: Temperature: 10°C~+50°C Related Humidity: ≤95% (40±2°C)