Supply 16 Zone, Conventional Fire Alarm System Control Panel PY-CK1016

Click image to view original picture
Product/Service: 16 Zone, Conventional Fire Alarm System Control Panel PY-CK1016  
Brand: Proyu 
Unit Price: Negotiating  Inquiry
The min order:  
Total Supply: 10000
Delivery Expiry: Delivery within 3 days after payment from buyer
Validity Period: Longterm Validity
Last Update: 2014-05-22
Browse: 2010
Basic Info of Company
 
 
Product detailed description

1.relays standard:Alarm,Trouble and Supervisory,Form-C
2. Initiating Device Circuits:Four Style B (Class B)

 16 Zone, Conventional Fire Alarm System Control Panel PY-CK1016

This Series Conventional Fire Alarm Control Panel

is a 24 volt, four, eight, sixteen-zone, Class B,

Conventional Fire Alarm Control Panel. Designed

exclusively to meet the latest market requirements and

future ULC codes, the highly cost-effective CK1000 Series

can be used in a variety of low- to mid-sized applications.

FEATURES

l Four to Sixteen Style B (Class B) Initiating Device

Circuits (IDCs).

– All zones accept two-wire smoke detectors and any

normally-open contact devices.

– Zones 1 - 16 configured as general alarm zones.

l All circuits are power-limited and supervised, meeting

the latest ULC requirements using fuseless technology.

l Two built-in, Style Y (Class B) Notification Appliance

(Signal) Circuits (NACs).

l NACs may be programmed:

– Silenceable.

– Non-Silenceable.

– Auto-Silence (program 5 to 20 minutes).

l 1.25 amps of NAC power.

l 3.0 amps of total system power.

l Alarm, Trouble and Supervisory, relay output.

l 24-volt operation.

l Resettable four-wire smoke detector power @ 500 mA.

l Non-resettable power @ 500 mA.

l Integral battery charger capable of charging up to 18

AH batteries (batteries over 4 AH require use of the

external battery backbox, or ULC listed equivalent).

l Disable/Enable control per IDC.

l Reverse polarity protection.

l Control buttons:

– Mode

– Test

– ACK (Acknowledge) Alarm Silence

– Reset

l LED indicators:

– AC Power(green & yellow LED)

– Fire Alarm(red LED)

– Trouble(yellow LED)

– Supervisory(yellow LED)

– Signal Silence(yellow LED)

– Battery Power(green & yellow LED)

– Zone Disable(yellow LED)

– NAC Fault(yellow LED)

– NAC Disable(yellow LED)

– Zone Alarm(one for each zone) (red LED)

– Zone Trouble(one for each zone) (yellow LED)

– Earth Fault (on circuit board)

– Battery Fault (on circuit board)

– Charger Fault (on circuit board

SPECIFICATIONS

l AC POWER

– 90~270 VAC, 50 Hz, 2.0 amps.

– Wire size: minimum 14 AWG (2.0 mm2) with 600-volt insulation.

l BATTERY

– Sealed lead-acid batteries only.

– Maximum charging circuit: 27.6VDC@ 0.8 amp for

normal flat charge.

– Maximum battery charger capacity: 18AH battery.

NOTE: two 4AH batteries can be housed in the cabinet. Larger

batteries require a separate battery box.

l Total 24 V system power: 3.0 amps.

l Notification appliance (signal) power: 2.5 amps.

l Maximum current per NAC: 1.25 amps (expandable to 2.5

amps).

l Maximum battery charging capability: 18 AH.

 Auxiliary Outputs
l Resettable four-wire smoke detector power@ 500 mA.
l Non-resettable power @ 500 mA.
NOTE: Total current for auxiliary power outputs and two NACs
must not exceed 3.0 amps. .
l Integral Form-C Alarm, Trouble and Supervisory relays,
rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30
VAC (resistive).

 