1.relays standard:Alarm,Trouble and Supervisory,Form-C
2. Initiating Device Circuits:Four Style B (Class B)
16 Zone, Conventional Fire Alarm System Control Panel PY-CK1016
This Series Conventional Fire Alarm Control Panel
is a 24 volt, four, eight, sixteen-zone, Class B,
Conventional Fire Alarm Control Panel. Designed
exclusively to meet the latest market requirements and
future ULC codes, the highly cost-effective CK1000 Series
can be used in a variety of low- to mid-sized applications.
FEATURES
l Four to Sixteen Style B (Class B) Initiating Device
Circuits (IDCs).
– All zones accept two-wire smoke detectors and any
normally-open contact devices.
– Zones 1 - 16 configured as general alarm zones.
l All circuits are power-limited and supervised, meeting
the latest ULC requirements using fuseless technology.
l Two built-in, Style Y (Class B) Notification Appliance
(Signal) Circuits (NACs).
l NACs may be programmed:
– Silenceable.
– Non-Silenceable.
– Auto-Silence (program 5 to 20 minutes).
l 1.25 amps of NAC power.
l 3.0 amps of total system power.
l Alarm, Trouble and Supervisory, relay output.
l 24-volt operation.
l Resettable four-wire smoke detector power @ 500 mA.
l Non-resettable power @ 500 mA.
l Integral battery charger capable of charging up to 18
AH batteries (batteries over 4 AH require use of the
external battery backbox, or ULC listed equivalent).
l Disable/Enable control per IDC.
l Reverse polarity protection.
l Control buttons:
– Mode
– Test
– ACK (Acknowledge) Alarm Silence
– Reset
l LED indicators:
– AC Power(green & yellow LED)
– Fire Alarm(red LED)
– Trouble(yellow LED)
– Supervisory(yellow LED)
– Signal Silence(yellow LED)
– Battery Power(green & yellow LED)
– Zone Disable(yellow LED)
– NAC Fault(yellow LED)
– NAC Disable(yellow LED)
– Zone Alarm(one for each zone) (red LED)
– Zone Trouble(one for each zone) (yellow LED)
– Earth Fault (on circuit board)
– Battery Fault (on circuit board)
– Charger Fault (on circuit board
SPECIFICATIONS
l AC POWER
– 90~270 VAC, 50 Hz, 2.0 amps.
– Wire size: minimum 14 AWG (2.0 mm2) with 600-volt insulation.
l BATTERY
– Sealed lead-acid batteries only.
– Maximum charging circuit: 27.6VDC@ 0.8 amp for
normal flat charge.
– Maximum battery charger capacity: 18AH battery.
NOTE: two 4AH batteries can be housed in the cabinet. Larger
batteries require a separate battery box.
l Total 24 V system power: 3.0 amps.
l Notification appliance (signal) power: 2.5 amps.
l Maximum current per NAC: 1.25 amps (expandable to 2.5
amps).
l Maximum battery charging capability: 18 AH.
Auxiliary Outputs
l Resettable four-wire smoke detector power@ 500 mA.
l Non-resettable power @ 500 mA.
NOTE: Total current for auxiliary power outputs and two NACs
must not exceed 3.0 amps. .
l Integral Form-C Alarm, Trouble and Supervisory relays,
rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30
VAC (resistive).