1 Loop 255points (it is also available for 2/3/4 loops).
Intelligent bus control mode; maximum 255 addressable points per loop, max 4 loops, max 48 zones
Color menu display interface
Loop card type design:1-4 loop card can be selected
Glass fuse per loop
Black box function
Independent controlling password for the specially needed gas recharging units
Self-design loop protocol
Wall-mounted structure, compact and exquisite
Language: simplified Chinese and English
Approvals:LPCB(EN54-2/4) CE
https://vedardalarm.com/intelligent-fire-control-panel-lpcb-fire-controller-p-248
Technical Specifications
Mains supply AC230V (50HZ),Voltage range: +10%~-15%
Standby battery 12V/12AH sealed lead acid battery *2
LCD screen size 7-inch color LCD screen
Operating Environment Temperature: -5°C~+50°C;Relative Humidity: ≤95%, non-condensing
Capacity 1020 addressable points
Communication Interface RS232, RS485, C A N, U S B
Dimension (L×W×H) 420mm×140mm×560mm
Output Five output. Fault output. 24V power output. Loop output