DIN EN 60332-1-2 / EN 60332-1-2 Fire test on a single cable

Zoom  Zoom Issue Date:2014-08-14   Browse:2784
 DIN EN 60332-1-2 / EN 60332-1-2 Fire test on a single cable 

DIN EN 60332-1-2 Fire test on a single cable - Standard 

DIN EN60332-1-2: Test for vertical flame propagation for a single insulated wire or cable 

DIN EN 60332-1-2 Fire test on a single cable - Test condition 

Before testing, all test pieces was conditioned at (23±5) ℃ for not less than 16h at a relative humidity of (50±20) %. 

DIN EN 60332-1-2 Fire test on a single cable- Requirement

When insulated wires and cables, the test is passed, if the distance between the lower end of the upper mounting and the start of charring more is over 50 mm. The flame expands by more than 540 mm from the bottom of the upper attachment to below, this must be called an error. Shall one failure recorded, two further tests perform. If both tests are passed, then the examination of individual wire or cable as passed. (Refer to DIN 5510-2 or EN 45545-2 test standard) 

DIN EN 60332-1-2 Fire test on a single cable - Reference Standard 

EN45545-2: Fire protection of railway vehicles - Part 2: Requirement for fire behaviors of materials and components 

DIN5510-2: Preventive fire protection in railway vehicles; Part 2: Fire behavior and fire side effects of materials and parts, classification, requirement and test methods

 EN 60332-3-24Tests on electric and optical fibre cables under fire conditions - Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables -Category C 

DIN EN 50266-2-4:: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Category C 

EN 50266-2-5: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Category D 

EN 61034-1, Measurement of smoke density of cables burning under defined conditions -Part 1: Test apparatus

EN 61034-2, Measurement of smoke density of cables burning under defined conditions - Part 2: Test procedure and requirements 

EN 50305Railway rolling stock cables having special fire performance -Test methods

 
 